Overview Sensor OID`s

Read here, how about you check your network metrics and status reports from the intelligent sensors. If you have SNMP monitoring in terms of questions, are you monitoring specialists from the house like Didactum ® and advice available.

Under an OID refers to an "Object Identifier". In the area of network monitoring, the OID is used to identify a stored in the Management Information Base (MIB) object. The MIB is a database that manages the devices on a network management system (NMS). In this case, the OID's are used to identify the AKCP intelligent sensors. Simply put, each OID identifies a variable that can be read or controlled by an SNMP command.
Here is a selection of AKCP sensors to monitor the security of data center and server room. Measure and monitor environmental parameters such as temperature, humidity, water, smoke, exercise and much more.

Intelligent environmental sensors: Description of the sensor OID `s

Three groups of OID of AKCP intelligent sensors
The AKCP intelligent sensors are divided into three groups (AC).
IMPORTANT: All intelligent sensors in the same group have the same OID.
Group A:
Group A includes the OID `s the only AKCP AKCP intelligent sensors temperature sensors, such as AK-TMP01, TMP00 or AK-TMPW15:

sensorProbeTempDegree = 1.3.6.1.4.1.3854.1.2.2.1.16.1.3.X
sensorProbeTempStatus = 1.3.6.1.4.1.3854.1.2.2.1.16.1.4.X
Group B:
The group of OIDs B of AKCP intelligent sensors consists of the analog AKCP sensors such as humidity, Airflow, 4-20mA Sensor Converter and AC-DC Sensor:

sensorProbeHumidityPercent = 1.3.6.1.4.1.3854.1.2.2.1.17.1.3.X
sensorProbeHumidityStatus = 1.3.6.1.4.1.3854.1.2.2.1.17.1.4.X
Group C:
Group C of the OID `s the AKCP intelligent sensors includes sensors, such as water sensor, sensor dry contact, motion detector, security sensor, AC-DC voltage, sensor relays and alarm siren:

sensor test switch status = 1.3.6.1.4.1.3854.1.2.2.1.18.1.3.X
Note: X is the port-number from 0 to 7 for the AKCP sensorProbe8 (AK-SP8) or from 0 to 27 for the connection ports such as the AKCP sensorProbe8-X20 (AK-SP8-X20).
The AKCP sensorProbe8-X20 offers an additional 20 ports to monitor dry contact. When state changes / incidents you will receive an alert via email, SMS (via email to SMS gateway) or SNMP trap.
Example:
The OID value .1.3.6.1.4.1.3854.1.2.2.1.16.1.3.0 AKCP stands for a temperature sensor of the group A, which was connected to the first RJ-45 connection port (0) AKCP the alarm hardware.

Important Note: The AKCP dual temperature sensors and humidity sensors consist of a temperature sensor of the group A and the humidity sensor of the group B.
List of OID's for temperature sensors on one sensorProbe8 (AK-SP8):

Here is the list of OID `s for the AKCP temperature sensors which were attached for example on a AKCP sensorProbe8 (AK-SP8):

.1.3.6.1.4.1.3854.1.2.2.1.16.1.3.0 Temperature sensor on port 1 .1.3.6.1.4.1.3854.1.2.2.1.16.1.3.1 Temperature sensor on Port 2 .1.3.6.1.4.1.3854.1.2.2.1.16.1.3.2 Temperature sensor on Port 3
... ...
.1.3.6.1.4.1.3854.1.2.2.1.16.1.3.7 Temperature sensor on port 8