SNMP OIDs for the sensorProbe units are as follows:
sensorProbeSwitchWaterRopeLeakLocation .1.3.6.1.4.1.3854.1.2.2.1.18.1.49.X sensorProbeSwitchWaterRopeLength .1.3.6.1.4.1.3854.1.2.2.1.18.1.50.X sensorProbeSwitchWaterRopeUnit .1.3.6.1.4.1.3854.1.2.2.1.18.1.51.X sensorProbeSwitchWaterRopeOhmPerUnit .1.3.6.1.4.1.3854.1.2.2.1.18.1.52.X sensorProbeSwitchWaterRopeRaw .1.3.6.1.4.1.3854.1.2.2.1.18.1.53.
X where X is port-1
SNMP OIDs for the securityProbe units are as follows:
sensorWaterRopeDescription .1.3.6.1.4.1.3854.2.3.21.1.2.Y
sensorWaterRopeStatus .1.3.6.1.4.1.3854.2.3.21.1.6.Y
sensorWaterRopeGoOffline .1.3.6.1.4.1.3854.2.3.21.1.8.Y
sensorWaterRopeLeakLocation .1.3.6.1.4.1.3854.2.3.21.1.9.Y
sensorWaterRopeLength .1.3.6.1.4.1.3854.2.3.21.1.10.Y
sensorWaterRopeUnit .1.3.6.1.4.1.3854.2.3.21.1.11.Y
sensorWaterRopeRaw .1.3.6.1.4.1.3854.2.3.21.1.13.Y
where Y is sensor ID, the dynamically number is generated when the sensor plugged in. |